Cooling Coil


Cooling of the airstream is achieved by bringing it into contact with a cold surface. The cold surface is a cooling coil. The cooling coil can be either a direct expansion (DX) cooling coil which is the evaporator of a vapour compression chiller or it may be a water coil similar to the heating coil described before. It differs from the heating coil in that a mixture of water and antifreeze (glycol) circulates through it rather than hot water. This mixture is cooled using a chiller.

Waste Heat Rejection

Vapour compression chillers have been described previously. An alternative method of cooling called absorption cooling is also described previously.

This section will look at methods of condenser heat rejection. Chillers generate a large amount of waste heat. In a domestic refrigerator, which we have used as an example of an everyday chiller previously, the waste heat is simply allowed to enter the kitchen via the condenser coil at the rear of the refrigerator. However, in air conditioning systems the amounts of waste heat involved are too great and would cause serious overheating in the plant room. Because of this the waste heat must be safely rejected outside the building. There are three main ways in which waste heat is removed from the condenser. These are by using; air cooled condensers, evaporative condensers or water cooled condensers.



Air Cooled Condensers the figure have been described previously in their application to split air conditioning systems. They are predominantly used for smaller cooling loads (less than 100kW) although they are used for rejecting up to three times this value mainly due to the fact that water is not used in their operation. This means maintenance costs are low.





Evaporative Condensers. Are similar to air cooled condensers except that their heat rejection capacity is increased by spraying water over the condenser coil (as shown in the figure). As this water evaporates it absorbs heat. Cooling of the condenser coil is therefore achieved by both sensible and latent means. The practical implication of this is that the unit has a smaller physical size for a given heat rejection capacity than an air cooled condenser. The water circulating over the condenser is treated to prevent bacterial growth. In addition spray eliminators must be used to avoid water droplets, which may be contaminated, leaving the unit. Evaporative condensers can be used up to 500kW cooling capacity.


Water Cooled Condensers. Variations in ambient air temperature     cause changes in the efficiency of air cooled condensers (see IP2). A more temperature stable heat sink is water. Water cooled condensers make use of this by jacketing the condenser in a shell which is filled with water (as shown in the figure). The condenser passes its waste heat to the water increasing its temperature by about 5oC. The water is then pumped to a water to water plate heat exchanger. Water from a large nearby source, such as a canal, river, lake or sea is also circulated through this heat exchanger having first been strained and filtered. In this way the condenser cooling water only makes thermal contact with the heat sink water. The heat sink water having picked up heat from the condenser circuit is returned to the main body of water where the heat it carries is dispersed. The condenser cooling water
leaves the plate heat exchanger and returns once more to the condenser to pick up more waste heat. The use of bodies of water such as rivers and canals as a heat sink is subject to water authority approval.


Cooling Towers. In locations where there are no large bodies of water that can be used as a heat sink, the water cooled condenser is used in conjunction with a cooling tower. A cooling tower is a device which cools the condenser cooling water by evaporation before returning it to the condenser to collect more heat. Figure shows a forced draught cooling tower. It can be seen that the condenser cooling water is allowed to tumble down through the device whilst air is forced upwards through the cascading water by a fan.





The purpose of the tower is to enhance evaporative cooling of the condenser water. It does this by increasing the surface area of the water exposed to air. Evaporation is a surface effect so increasing the surface area of water in contact with the air increases evaporation. Water surface area increases are achieved in a number of ways such as by allowing the water to tumble down splash bars, by spraying or by running it over a PVC matrix. When the condenser water evaporates it absorbs latent heat from the water which is left behind. The effect of this is to cool the water which collects in the sump at the base of the tower. This is pumped back to the water cooled condenser to remove more waste heat.

Cooling Tower Hygiene is an important area of concern since the water temperatures in the tower are conducive to bacterial and algal growth. In particular legionnaires disease, which is a form of pneumonia, has been associated with wet heat rejection equipment. The legionella bacteria grow in the warm water of the cooling tower. They escape from the tower as part of the mist created by the flow of air and water through the tower. If ambient conditions are suitable and the bacteria carrying droplets are breathed in by a susceptible passer by a potentially fatal infection can occur. The problem is avoided by using air cooled condensers. However, dry heat rejection uses approximately 30% more energy for the same capacity as a wet method. Cooling towers can be used safely with the following Precautions:

• Use of spray eliminators to prevent the release of infected droplets
• The tower should be built of easily cleanable materials such as plastics or epoxy coatings with smooth surfaces. Access doors should be incorporated into the tower to facilitate cleaning.
• The tower should be positioned away from air intakes which could draw infected droplets into the building through the air conditioning system.
• A program of maintenance and cleaning should be carried out throughout the life of the tower. This should include dosing the cooling water with bactericides. Chemicals to prevent algal growth should also be used since algae tend to coat surfaces and give the legionella a medium on which to grow.