Local Comfort Cooling Systems (Split Air Conditioning Systems)


Split Air Conditioning Systems. Split air conditioning systems are so described because the evaporator is housed in a room unit and the condenser is housed in a separate outdoor unit. Refrigerant flow and return pipes connect the two units together. The indoor unit can be wall or floor mounted or accommodated within a suspended ceiling. The finish of the indoor unit is of high quality to integrate with the appearance of the room decor or suspended ceiling panels.

A diagram of a ceiling unit is shown in below figure. A fan is used to draw room air across the evaporator to provide the necessary cooling. Chilled air is then output via directional slots. These slots are adjusted to keep the cold airstream away from the room occupants so that cold draughts are avoided. The chilled air mixes with the room air outside the occupied zone. The mixed air eventually diffuses throughout the room to create the cooling effect.



The outdoor unit (below figure) contains the condenser which is air cooled. The condenser like the evaporator has its surface area increased using fins. A fan is used to draw outside air across the condenser to discharge the waste heat to atmosphere. The outdoor unit can be placed a considerable distance (up to 50m pipe length including 30m vertical rise) from the indoor unit. This allows flexibility of design and sympathetic positioning of the outdoor units on the external surfaces of the building.



Multi split air conditioning. Is based on the same principle as single split air conditioning except that up to four indoor units can be served by a single outdoor unit. Each indoor unit has its own set of refrigerant pipe work connecting it to the outdoor unit. All of the indoor units operate in the same mode i.e. all heating or all cooling, although individual control of the degree of heating or cooling from off to full output can be exercised over each unit. Some indoor units are fitted with electric heaters so that whilst the multi split group is operating in cooling mode odd single units can provide a degree of heating.